• 2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator
  • 2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator
  • 2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator
  • 2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator
  • 2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator
  • 2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator

2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator

After-sales Service: Global Service Policy
Warranty: 1 Year or 2000 Hours
Type: Self-Starting Diesel Generator
Installation Method: Fixed
Stroke: Four Stroke
Cooling Method: Water Cooling
Customization:
Diamond Member Since 2016

Suppliers with verified business licenses

Trading Company

Basic Info.

Model NO.
M2250G
Output Type
AC Three Phase
Speed
Speed
Conditions of Use
Land Use
Usage
Common Units, Standby Unit
Landuse Type of Unit
Ordinary
Excitation Mode
AC Rotating Exciter
Technology
World Latest Technology
Quality
Powerful Service
Performance
Reliable Running
Warranty Time
6000 Hours
Cost
Competitive Price
Appearance
Stable Working
Engine
Original Germany Mtu Brand
Function
Continuous Power Supply
Application
Power Plant Source
Transport Package
Plastic
Specification
Max 2250KVA, , Leroy Somer, Deepsea
Trademark
Mains Power
Origin
Germany
HS Code
8502131000
Production Capacity
5units/Month

Product Description

Mitsubishi engines with high-strength design, working endurably, Stably and reliably.
Tolerance for impact resistance and output sufficient.
Low fuel consumption, low vibration and noise, simple and low cost maintenance
Power range within 710-3300KVA

Genset model:   M2250G
Standby power: 2250KVA/1800KW
Rated power:    2050KVA/1640KW
50HZ, 1500RPM, 230/400V, 3 phase 4 wire, 16 cylinder Vee type,
Engine model:   16V4000G23  
Alternator:  Leroy Somer, MECC, Stamford, Marathon, Siemens
Controller:  Deepsea, ComAp, Woodward, DEIF
MCCB:      ABB, CHINT, DELIXI
ATS:         ABB,  Socomec
Type:    Weatherproof, Soundproof, enclosure, containerized canopy
Application:   Synchronizing system for multi-genset, Paralleling system with Grid
 
ENGINE BASIC DATA           LUBRICANTION SYSTEM      
NO. of Sylinder & type 16  Vee type   Oil pressure @ rated speed (kpa)   420-550
Air intake way Turbocharged   Lubrication system capacity(L)   300
Bore*Stroke(mm) 170*210   Operating temperature (ºC)   89-95
Displacement (L) 76.3   CONSUMPTION      
Displacement per cylinder (L) 4.77   110% (L/h) 1800KW / 2250KVA 444
Compression ratio 16.5 : 1   100% (L/h) 1640KW / 2050KVA 406
Rated speed(RPM) 1500   75% (L/h) 1230KW / 1537.5KVA 314
Rated power(KW) 1798KW (2247.5KVA)   50% (L/h) 820KW / 1025KVA 217
Gross power(KW) 1978KW
(2472.5KVA)
  25% (L/h) 410KW / 512.5KVA 121
Electronic Governor type ADEC & SAM   Oil consumption(% of fuel consumption per hour)    
Piston speed(m/s) 10.5   0.3%
Mean effective pressure(kPa) 18.9   COOLING SYSTEM      
Intake air depression(mbar)     15 / 50   Coolant temperature (ºC)   100
Exhaust back pressure     30 / 85   Coolant capacity (L)   225
FUEL SYSTEM           Coolant flow rate (m3/h)   68.5
Fuel Injection System     Electronic   Coolant pump, inletpressure(bar) 0.2 / 1.5
Pressure at return connection 0.5 bar (max)   Height above engine, max (m) 15
Fuel supply flow(L/h) max     840   Operating pressure (bar) 2.5
Fuel return flow(L/h) max     360   Thermostat temperature (ºC)   79
COMBUSTION AIR/EXHAUST GAS           ELECTRIC SYSTEM      
Burning capacity(m3/min)     138   Battery  2*12V
Max back pressure (kPa)     8.5   Startor motor (V)   24V, 19KW
Exhaust temperature (ºC)     480   Start attempt duration, mas.(s)   30
Exhaust flow (m3/s)     7.4   Startor, power requirement at firing speed (A)    
Cooling way Water-air cooling   800
 
Germany MTU Diesel Generator Model List:
(Standard MTU Generator Supply Scope)
50HZ, 1500RPM, 380-415V, 3 phase 4 wire, 
Genset Model Standby power Prime power Engine Model Alternator model
Leroy Somer
Dimension (L*W*H mm)
KVA KW KVA KW
M725G 725 580 650 520 12V2000G25 LSA49.1S4 4200*1600*2250
M900G 900 720 800 640 12V2000G65 LSA49.1M75 4200*1600*2250
M1000G 1000 800 910 728 16V2000G25 LSA49.1L10 4500*1800*2300
M1100G 1100 880 1000 800 16V2000G65 LSA50.2S3 4500*1800*2300
M1250G 1250 1000 1135 908 18V2000G65 LSA50.2M6 4700*1900*2350
M1375G 1375 1100 1250 1000 12V4000G21R LSA50.2M6 6150*2150*2400
M1540G 1540 1232 1400 1120 12V4000G23R LSA50.2L8 6150*2150*2400
M1800G 1800 1440 1640 1312 12V4000G23 LSA50.2V10 6200*2150*2400
M2000G 2000 1600 1812 1450 12V4000G63 LSA51.2S55 6200*2150*2400
M2250G 2250 1800 2050 1640 16V4000G23 LSA51.2L70 6500*2600*2800
M2500G 2500 2000 2250 1800 16V4000G63 LVSI804S 6600*2600*2800
M2750G 2750 2200 2500 2000 20V4000G23 LVS1804R 7600*2600*3000
M3000G 3000 2400 2750 2200 20V4000G63 LVS1804S 7600*2600*3000
M3300G 3300 2640 3000 2400 20V4000G63L LVS1824G 7600*2600*3000
 
60HZ, 1800RPM, 380-480V, 3 phase 4 wire, 
M880G6 880 704 800 640 12V2000G45 LSA49.1 S4 4200*1650*2280
M1000G6 1000 800 910 728 12V2000G85 LSA49.1 M75 4200*1650*2280
M1100G6 1100 880 1000 800 16V2000G45 LSA49.1 L9 4500*2000*2300
M1250G6 1250 1000 1125 900 16V2000G85 HCI634H 4500*2000*2300
M1450G6 1450 1160 1300 1040 18V2000G85 LSA50.2 S4 4750*2000*2380
M1900G6 1875 1500 1700 1360 12V4000G43 LSA50.2 L7 6150*2150*2400
M2250G6 2250 1600 2000 1600 12V4000G83 LSA50.2 VL10 6150*2150*2400
M2500G6 2500 2000 2250 1800 16V4000G43 PI734E 6500*2600*2500
M2750G6 2750 2200 2500 2000 16V4000G83 LSA51.2 L70 6550*2600*2500
M3000G6 3000 2400 2750 2200 20V4000G43 PI734G 7600*2600*3000

2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator
2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator2250kVA 1800kw Output Power Germany Mtu Engine Diesel Generator
 

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now

You Might Also Like

Diamond Member Since 2016

Suppliers with verified business licenses

Trading Company
Management System Certification
ISO 9001, ISO 14001